Your Preferred Rittal Partner

J&M Eastern Group is a Rittal supplier in Malaysia that specialises in Rittal Products. As one of the top Rittal partner and reseller in Malaysia, we carry a wide range of Rittal products such as enclosures, power distributions, climate control, and IT infrastructure to meet your requirements and quickly respond to the demands of your business. Our team is well experienced with Rittal products, solutions and services.

Rittal Home. Complex made simple – the guiding principle that makes Rittal perfect partner for you. – Enclosures, Power distribution, Climate control, IT infrastructure, Software & services, Automation.

Blue e+ fan-and-filter unit

Blue e+ fan-and-filter unit

Complete fan unit for tool-free mounting on surfaces. Air throughput from 20 - 1160 m³/h, standard protection category IP 54.

Blue e+ fan-and-filter unit comparison

Rittal SK 3237700
Rittal SK 3237700
Article number:
SK 3237.700
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including chopped-fibre filter mat
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 20 m³/h

At 60 Hz: 25 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 15 m³/h

At 60 Hz: 18 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 13 W

At 60 Hz: 11.1 W

Rated current max.
At 50 Hz: 0.1 A

At 60 Hz: 0.09 A

Dimensions
Width: 116.5 mm

Height: 116.5 mm

Depth: 64.5 mm

Installation depth
46 mm
Mounting cut-out
Cut-out width: 92 mm

Cut-out height: 92 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter
IP56 with chopped-fibre filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter
Type 3
Type 3R with chopped-fibre filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 42 dB(A)

At 60 Hz: 47 dB(A)

Weight/pack
0.4 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997776
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 20/25 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 116.5 x 116.5 x 64.5 mm, RAL 7035
Rittal SK 3237708
Rittal SK 3237708
Article number:
SK 3237.708
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including chopped-fibre filter mat
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 20 m³/h

At 60 Hz: 25 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 15 m³/h

At 60 Hz: 18 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 13 W

At 60 Hz: 11.1 W

Rated current max.
At 50 Hz: 0.1 A

At 60 Hz: 0.09 A

Dimensions
Width: 116.5 mm

Height: 116.5 mm

Depth: 64.5 mm

Installation depth
46 mm
Mounting cut-out
Cut-out width: 92 mm

Cut-out height: 92 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter
IP56 with chopped-fibre filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter
Type 3
Type 3R with chopped-fibre filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 42 dB(A)

At 60 Hz: 47 dB(A)

Weight/pack
0.4 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998308
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 20/25 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 116.5 x 116.5 x 64.5 mm, RAL 9005
Rittal SK 3237710
Rittal SK 3237710
Article number:
SK 3237.710
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including chopped-fibre filter mat
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 20 m³/h

At 60 Hz: 25 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 15 m³/h

At 60 Hz: 18 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 12 W

At 60 Hz: 10 W

Rated current max.
At 50 Hz: 0.14 A

At 60 Hz: 0.13 A

Dimensions
Width: 116.5 mm

Height: 116.5 mm

Depth: 64.5 mm

Installation depth
46 mm
Mounting cut-out
Cut-out width: 92 mm

Cut-out height: 92 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter
IP56 with chopped-fibre filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter
Type 3
Type 3R with chopped-fibre filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 42 dB(A)

At 60 Hz: 47 dB(A)

Weight/pack
0.4 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998292
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 20/25 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 116.5 x 116.5 x 64.5 mm, RAL 7035
Rittal SK 3237718
Rittal SK 3237718
Article number:
SK 3237.718
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including chopped-fibre filter mat
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 20 m³/h

At 60 Hz: 25 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 15 m³/h

At 60 Hz: 18 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 12 W

At 60 Hz: 10 W

Rated current max.
At 50 Hz: 0.14 A

At 60 Hz: 0.13 A

Dimensions
Width: 116.5 mm

Height: 116.5 mm

Depth: 64.5 mm

Installation depth
46 mm
Mounting cut-out
Cut-out width: 92 mm

Cut-out height: 92 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter
IP56 with chopped-fibre filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter
Type 3
Type 3R with chopped-fibre filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 42 dB(A)

At 60 Hz: 47 dB(A)

Weight/pack
0.4 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998285
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 20/25 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 116.5 x 116.5 x 64.5 mm, RAL 9005
Rittal SK 3237724
Rittal SK 3237724
Article number:
SK 3237.724
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including chopped-fibre filter mat
Fan
Axial, DC motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
With DC: 20 m³/h
Air throughput with matching outlet filter including chopped-fibre filter
With DC: 15 m³/h
Rated operating voltage
24 V (DC)
Power consumption Pel
With DC: 1.4 W
Rated current max.
With DC: 0.06 A
Dimensions
Width: 116.5 mm

Height: 116.5 mm

Depth: 64.5 mm

Installation depth
46 mm
Mounting cut-out
Cut-out width: 92 mm

Cut-out height: 92 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter
IP56 with chopped-fibre filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter
Type 3
Type 3R with chopped-fibre filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
With DC: 42 dB(A)
Weight/pack
0.24 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998278
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 20 m³/h, 24 V (DC), WHD 116.5 x 116.5 x 64.5 mm, RAL 7035
Rittal SK 3238700
Rittal SK 3238700
Article number:
SK 3238.700
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 53 m³/h

At 60 Hz: 64 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 63 m³/h

At 60 Hz: 72 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 40 m³/h

At 60 Hz: 46 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 49 m³/h

At 60 Hz: 55 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 14.7 W

At 60 Hz: 16.5 W

Rated current max.
At 50 Hz: 0.1 A

At 60 Hz: 0.12 A

Dimensions
Width: 148.5 mm

Height: 148.5 mm

Depth: 82.5 mm

Installation depth
64 mm
Mounting cut-out
Cut-out width: 124 mm

Cut-out height: 124 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 1 with pleated filter
Type 12 with chopped-fibre filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 52 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
0.68 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997615
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 63/72 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 148.5 x 148.5 x 82.5 mm, RAL 7035
Rittal SK 3238708
Rittal SK 3238708
Article number:
SK 3238.708
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 53 m³/h

At 60 Hz: 64 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 63 m³/h

At 60 Hz: 72 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 40 m³/h

At 60 Hz: 46 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 49 m³/h

At 60 Hz: 55 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 14.7 W

At 60 Hz: 16.5 W

Rated current max.
At 50 Hz: 0.1 A

At 60 Hz: 0.12 A

Dimensions
Width: 148.5 mm

Height: 148.5 mm

Depth: 82.5 mm

Installation depth
64 mm
Mounting cut-out
Cut-out width: 124 mm

Cut-out height: 124 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 1 with pleated filter
Type 12 with chopped-fibre filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 52 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
0.68 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997622
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 63/72 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 148.5 x 148.5 x 82.5 mm, RAL 9005
Rittal SK 3238710
Rittal SK 3238710
Article number:
SK 3238.710
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 53 m³/h

At 60 Hz: 64 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 63 m³/h

At 60 Hz: 72 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 40 m³/h

At 60 Hz: 46 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 49 m³/h

At 60 Hz: 55 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 15.4 W

At 60 Hz: 15.8 W

Rated current max.
At 50 Hz: 0.2 A

At 60 Hz: 0.21 A

Dimensions
Width: 148.5 mm

Height: 148.5 mm

Depth: 82.5 mm

Installation depth
64 mm
Mounting cut-out
Cut-out width: 124 mm

Cut-out height: 124 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 1 with pleated filter
Type 12 with chopped-fibre filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 52 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
0.68 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998247
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 63/72 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 148.5 x 148.5 x 82.5 mm, RAL 7035
Rittal SK 3238718
Rittal SK 3238718
Article number:
SK 3238.718
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 53 m³/h

At 60 Hz: 64 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 63 m³/h

At 60 Hz: 72 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 40 m³/h

At 60 Hz: 46 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 49 m³/h

At 60 Hz: 55 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 15.4 W

At 60 Hz: 15.8 W

Rated current max.
At 50 Hz: 0.2 A

At 60 Hz: 0.21 A

Dimensions
Width: 148.5 mm

Height: 148.5 mm

Depth: 82.5 mm

Installation depth
64 mm
Mounting cut-out
Cut-out width: 124 mm

Cut-out height: 124 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 1 with pleated filter
Type 12 with chopped-fibre filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 52 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
0.68 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998230
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 63/72 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 148.5 x 148.5 x 82.5 mm, RAL 9005
Rittal SK 3238724
Rittal SK 3238724
Article number:
SK 3238.724
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Axial, DC motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
With DC: 53 m³/h
Air throughput, unimpeded airflow (with pleated filter)
With DC: 63 m³/h
Air throughput with matching outlet filter including chopped-fibre filter
With DC: 40 m³/h
Air throughput with matching outlet filter including pleated filter
With DC: 49 m³/h
Rated operating voltage
24 V (DC)
Power consumption Pel
With DC: 5.7 W
Rated current max.
With DC: 0.27 A
Dimensions
Width: 148.5 mm

Height: 148.5 mm

Depth: 82.5 mm

Installation depth
64 mm
Mounting cut-out
Cut-out width: 124 mm

Cut-out height: 124 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 1 with pleated filter
Type 12 with chopped-fibre filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
With DC: 52 dB(A)
Weight/pack
0.42 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998223
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 63 m³/h, 24 V (DC), WHD 148.5 x 148.5 x 82.5 mm, RAL 7035
Rittal SK 3239700
Rittal SK 3239700
Article number:
SK 3239.700
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 100 m³/h

At 60 Hz: 115 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 110 m³/h

At 60 Hz: 125 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 75 m³/h

At 60 Hz: 86 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 92 m³/h

At 60 Hz: 104 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 14.7 W

At 60 Hz: 16.5 W

Rated current max.
At 50 Hz: 0.1 A

At 60 Hz: 0.12 A

Dimensions
Width: 204 mm

Height: 204 mm

Depth: 105 mm

Installation depth
84 mm
Mounting cut-out
Cut-out width: 177 mm

Cut-out height: 177 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 51 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
0.92 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998216
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 110/125 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 204 x 204 x 105 mm, RAL 7035
Rittal SK 3239708
Rittal SK 3239708
Article number:
SK 3239.708
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 100 m³/h

At 60 Hz: 115 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 110 m³/h

At 60 Hz: 125 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 75 m³/h

At 60 Hz: 86 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 92 m³/h

At 60 Hz: 104 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 14.7 W

At 60 Hz: 16.5 W

Rated current max.
At 50 Hz: 0.1 A

At 60 Hz: 0.12 A

Dimensions
Width: 204 mm

Height: 204 mm

Depth: 105 mm

Installation depth
84 mm
Mounting cut-out
Cut-out width: 177 mm

Cut-out height: 177 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 51 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
0.92 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998209
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 110/125 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 204 x 204 x 105 mm, RAL 9005
Rittal SK 3239710
Rittal SK 3239710
Article number:
SK 3239.710
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
1 cover (front)
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 100 m³/h

At 60 Hz: 115 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 110 m³/h

At 60 Hz: 125 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 75 m³/h

At 60 Hz: 86 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 92 m³/h

At 60 Hz: 104 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 15.4 W

At 60 Hz: 15.8 W

Rated current max.
At 50 Hz: 0.2 A

At 60 Hz: 0.21 A

Dimensions
Width: 204 mm

Height: 204 mm

Depth: 105 mm

Installation depth
84 mm
Mounting cut-out
Cut-out width: 177 mm

Cut-out height: 177 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 51 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
0.92 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998193
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 110/125 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 204 x 204 x 105 mm, RAL 7035
Rittal SK 3239718
Rittal SK 3239718
Article number:
SK 3239.718
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Axial, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 100 m³/h

At 60 Hz: 115 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 110 m³/h

At 60 Hz: 125 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 75 m³/h

At 60 Hz: 86 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 92 m³/h

At 60 Hz: 104 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 15.4 W

At 60 Hz: 15.8 W

Rated current max.
At 50 Hz: 0.2 A

At 60 Hz: 0.21 A

Dimensions
Width: 204 mm

Height: 204 mm

Depth: 105 mm

Installation depth
84 mm
Mounting cut-out
Cut-out width: 177 mm

Cut-out height: 177 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 51 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
0.92 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998186
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 110/125 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 204 x 204 x 105 mm, RAL 9005
Rittal SK 3239724
Rittal SK 3239724
Article number:
SK 3239.724
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Axial, DC motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
With DC: 100 m³/h
Air throughput, unimpeded airflow (with pleated filter)
With DC: 110 m³/h
Air throughput with matching outlet filter including chopped-fibre filter
With DC: 75 m³/h
Air throughput with matching outlet filter including pleated filter
With DC: 92 m³/h
Rated operating voltage
24 V (DC)
Power consumption Pel
With DC: 5.7 W
Rated current max.
With DC: 0.27 A
Dimensions
Width: 204 mm

Height: 204 mm

Depth: 105 mm

Installation depth
84 mm
Mounting cut-out
Cut-out width: 177 mm

Cut-out height: 177 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-15 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
With DC: 51 dB(A)
Weight/pack
0.66 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998179
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 110 m³/h, 24 V (DC), WHD 204 x 204 x 105 mm, RAL 7035
Rittal SK 3240700
Rittal SK 3240700
Article number:
SK 3240.700
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 175 m³/h

At 60 Hz: 157 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 218 m³/h

At 60 Hz: 191 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 130 m³/h

At 60 Hz: 112 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 191 m³/h

At 60 Hz: 161 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 33.1 W

At 60 Hz: 37.3 W

Rated current max.
At 50 Hz: 0.2 A

At 60 Hz: 0.21 A

Dimensions
Width: 255 mm

Height: 255 mm

Depth: 129 mm

Installation depth
108 mm
Mounting cut-out
Cut-out width: 224 mm

Cut-out height: 224 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 48 dB(A)

At 60 Hz: 45 dB(A)

Weight/pack
1.82 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998148
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 218/191 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 255 x 255 x 129 mm, RAL 7035
Rittal SK 3240708
Rittal SK 3240708
Article number:
SK 3240.708
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 175 m³/h

At 60 Hz: 157 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 218 m³/h

At 60 Hz: 191 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 130 m³/h

At 60 Hz: 112 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 191 m³/h

At 60 Hz: 161 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 33.1 W

At 60 Hz: 37.3 W

Rated current max.
At 50 Hz: 0.2 A

At 60 Hz: 0.21 A

Dimensions
Width: 255 mm

Height: 255 mm

Depth: 129 mm

Installation depth
108 mm
Mounting cut-out
Cut-out width: 224 mm

Cut-out height: 224 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 48 dB(A)

At 60 Hz: 45 dB(A)

Weight/pack
1.82 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998131
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 218/191 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 255 x 255 x 129 mm, RAL 9005
Rittal SK 3240710
Rittal SK 3240710
Article number:
SK 3240.710
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 175 m³/h

At 60 Hz: 157 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 218 m³/h

At 60 Hz: 191 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 130 m³/h

At 60 Hz: 112 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 191 m³/h

At 60 Hz: 161 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 35.5 W

At 60 Hz: 38.2 W

Rated current max.
At 50 Hz: 0.41 A

At 60 Hz: 0.42 A

Dimensions
Width: 255 mm

Height: 255 mm

Depth: 129 mm

Installation depth
108 mm
Mounting cut-out
Cut-out width: 224 mm

Cut-out height: 224 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 48 dB(A)

At 60 Hz: 45 dB(A)

Weight/pack
1.82 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998124
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 218/191 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 255 x 255 x 129 mm, RAL 7035
Rittal SK 3240718
Rittal SK 3240718
Article number:
SK 3240.718
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 175 m³/h

At 60 Hz: 157 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 218 m³/h

At 60 Hz: 191 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 130 m³/h

At 60 Hz: 112 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 191 m³/h

At 60 Hz: 161 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 35.5 W

At 60 Hz: 38.2 W

Rated current max.
At 50 Hz: 0.41 A

At 60 Hz: 0.42 A

Dimensions
Width: 255 mm

Height: 255 mm

Depth: 129 mm

Installation depth
108 mm
Mounting cut-out
Cut-out width: 224 mm

Cut-out height: 224 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 48 dB(A)

At 60 Hz: 45 dB(A)

Weight/pack
1.82 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998117
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 218/191 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 255 x 255 x 129 mm, RAL 9005
Rittal SK 3240724
Rittal SK 3240724
Article number:
SK 3240.724
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, DC motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
With DC: 175 m³/h
Air throughput, unimpeded airflow (with pleated filter)
With DC: 218 m³/h
Air throughput with matching outlet filter including chopped-fibre filter
With DC: 130 m³/h
Air throughput with matching outlet filter including pleated filter
With DC: 191 m³/h
Rated operating voltage
24 V (DC)
Power consumption Pel
With DC: 10.1 W
Rated current max.
With DC: 0.42 A
Dimensions
Width: 255 mm

Height: 255 mm

Depth: 129 mm

Installation depth
108 mm
Mounting cut-out
Cut-out width: 224 mm

Cut-out height: 224 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
With DC: 48 dB(A)
Weight/pack
1.44 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998100
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 218 m³/h, 24 V (DC), WHD 255 x 255 x 129 mm, RAL 7035
Rittal SK 3241700
Rittal SK 3241700
Article number:
SK 3241.700
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 225 m³/h

At 60 Hz: 245 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 272 m³/h

At 60 Hz: 280 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 173 m³/h

At 60 Hz: 187 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 242 m³/h

At 60 Hz: 246 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 43.2 W

At 60 Hz: 54.5 W

Rated current max.
At 50 Hz: 0.27 A

At 60 Hz: 0.32 A

Dimensions
Width: 255 mm

Height: 255 mm

Depth: 129 mm

Installation depth
108 mm
Mounting cut-out
Cut-out width: 224 mm

Cut-out height: 224 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 53 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
1.8 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998063
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 272/280 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 255 x 255 x 129 mm, RAL 7035
Rittal SK 3241708
Rittal SK 3241708
Article number:
SK 3241.708
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 225 m³/h

At 60 Hz: 245 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 272 m³/h

At 60 Hz: 280 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 173 m³/h

At 60 Hz: 187 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 242 m³/h

At 60 Hz: 246 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 43.2 W

At 60 Hz: 54.5 W

Rated current max.
At 50 Hz: 0.27 A

At 60 Hz: 0.32 A

Dimensions
Width: 255 mm

Height: 255 mm

Depth: 129 mm

Installation depth
108 mm
Mounting cut-out
Cut-out width: 224 mm

Cut-out height: 224 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 53 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
1.8 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998056
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 272/280 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 255 x 255 x 129 mm, RAL 9005
Rittal SK 3241710
Rittal SK 3241710
Article number:
SK 3241.710
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 225 m³/h

At 60 Hz: 245 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 272 m³/h

At 60 Hz: 280 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 173 m³/h

At 60 Hz: 187 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 242 m³/h

At 60 Hz: 246 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 43.4 W

At 60 Hz: 52.2 W

Rated current max.
At 50 Hz: 0.54 A

At 60 Hz: 0.6 A

Dimensions
Width: 255 mm

Height: 255 mm

Depth: 129 mm

Installation depth
108 mm
Mounting cut-out
Cut-out width: 224 mm

Cut-out height: 224 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 53 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
1.8 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998049
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 272/280 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 255 x 255 x 129 mm, RAL 7035
Rittal SK 3241718
Rittal SK 3241718
Article number:
SK 3241.718
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, shaded pole motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 225 m³/h

At 60 Hz: 245 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 272 m³/h

At 60 Hz: 280 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 173 m³/h

At 60 Hz: 187 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 242 m³/h

At 60 Hz: 246 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 43.4 W

At 60 Hz: 52.2 W

Rated current max.
At 50 Hz: 0.54 A

At 60 Hz: 0.6 A

Dimensions
Width: 255 mm

Height: 255 mm

Depth: 129 mm

Installation depth
108 mm
Mounting cut-out
Cut-out width: 224 mm

Cut-out height: 224 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 53 dB(A)

At 60 Hz: 54 dB(A)

Weight/pack
1.8 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998032
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 272/280 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 255 x 255 x 129 mm, RAL 9005
Rittal SK 3241724
Rittal SK 3241724
Article number:
SK 3241.724
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, DC motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
With DC: 225 m³/h
Air throughput, unimpeded airflow (with pleated filter)
With DC: 272 m³/h
Air throughput with matching outlet filter including chopped-fibre filter
With DC: 173 m³/h
Air throughput with matching outlet filter including pleated filter
With DC: 242 m³/h
Rated operating voltage
24 V (DC)
Power consumption Pel
With DC: 19.1 W
Rated current max.
With DC: 0.8 A
Dimensions
Width: 255 mm

Height: 255 mm

Depth: 129 mm

Installation depth
108 mm
Mounting cut-out
Cut-out width: 224 mm

Cut-out height: 224 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
With DC: 53 dB(A)
Weight/pack
1.6 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177998025
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 272 m³/h, 24 V (DC), WHD 255 x 255 x 129 mm, RAL 7035
Rittal SK 3243700
Rittal SK 3243700
Article number:
SK 3243.700
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, 1~ capacitor motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 540 m³/h

At 60 Hz: 590 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 625 m³/h

At 60 Hz: 716 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 444 m³/h

At 60 Hz: 498 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 565 m³/h

At 60 Hz: 645 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 77.7 W

At 60 Hz: 106.4 W

Rated current max.
At 50 Hz: 0.39 A

At 60 Hz: 0.47 A

Dimensions
Width: 323 mm

Height: 323 mm

Depth: 144.5 mm

Installation depth
124 mm
Mounting cut-out
Cut-out width: 292 mm

Cut-out height: 292 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 62 dB(A)

At 60 Hz: 65 dB(A)

Weight/pack
3.12 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997981
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 625/716 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 323 x 323 x 144.5 mm, RAL 7035
Rittal SK 3243708
Rittal SK 3243708
Article number:
SK 3243.708
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, 1~ capacitor motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 540 m³/h

At 60 Hz: 590 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 625 m³/h

At 60 Hz: 716 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 444 m³/h

At 60 Hz: 498 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 565 m³/h

At 60 Hz: 645 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 77.7 W

At 60 Hz: 106.4 W

Rated current max.
At 50 Hz: 0.39 A

At 60 Hz: 0.47 A

Dimensions
Width: 323 mm

Height: 323 mm

Depth: 144.5 mm

Installation depth
124 mm
Mounting cut-out
Cut-out width: 292 mm

Cut-out height: 292 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 62 dB(A)

At 60 Hz: 65 dB(A)

Weight/pack
3.12 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997974
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 625/716 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 323 x 323 x 144.5 mm, RAL 9005
Rittal SK 3243710
Rittal SK 3243710
Article number:
SK 3243.710
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, 1~ capacitor motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 540 m³/h

At 60 Hz: 590 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 625 m³/h

At 60 Hz: 716 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 444 m³/h

At 60 Hz: 498 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 565 m³/h

At 60 Hz: 645 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 78.7 W

At 60 Hz: 102.8 W

Rated current max.
At 50 Hz: 0.81 A

At 60 Hz: 0.9 A

Dimensions
Width: 323 mm

Height: 323 mm

Depth: 144.5 mm

Installation depth
124 mm
Mounting cut-out
Cut-out width: 292 mm

Cut-out height: 292 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 6 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 62 dB(A)

At 60 Hz: 65 dB(A)

Weight/pack
3.12 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997967
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 625/716 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 323 x 323 x 144.5 mm, RAL 7035
Rittal SK 3243718
Rittal SK 3243718
Article number:
SK 3243.718
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, 1~ capacitor motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 540 m³/h

At 60 Hz: 590 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 625 m³/h

At 60 Hz: 716 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 444 m³/h

At 60 Hz: 498 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 565 m³/h

At 60 Hz: 645 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 78.7 W

At 60 Hz: 102.8 W

Rated current max.
At 50 Hz: 0.81 A

At 60 Hz: 0.9 A

Dimensions
Width: 323 mm

Height: 323 mm

Depth: 144.5 mm

Installation depth
124 mm
Mounting cut-out
Cut-out width: 292 mm

Cut-out height: 292 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 6 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 62 dB(A)

At 60 Hz: 65 dB(A)

Weight/pack
3.12 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997950
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 625/716 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 323 x 323 x 144.5 mm, RAL 9005
Rittal SK 3244700
Rittal SK 3244700
Article number:
SK 3244.700
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, 1~ capacitor motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 700 m³/h

At 60 Hz: 770 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 867 m³/h

At 60 Hz: 910 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 537 m³/h

At 60 Hz: 587 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 720 m³/h

At 60 Hz: 745 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 114.4 W

At 60 Hz: 153.5 W

Rated current max.
At 50 Hz: 0.51 A

At 60 Hz: 0.68 A

Dimensions
Width: 323 mm

Height: 323 mm

Depth: 156 mm

Installation depth
136 mm
Mounting cut-out
Cut-out width: 292 mm

Cut-out height: 292 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 64 dB(A)

At 60 Hz: 66 dB(A)

Weight/pack
3.84 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997912
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 867/910 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 323 x 323 x 156 mm, RAL 7035
Rittal SK 3244708
Rittal SK 3244708
Article number:
SK 3244.708
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, 1~ capacitor motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 700 m³/h

At 60 Hz: 770 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 867 m³/h

At 60 Hz: 910 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 537 m³/h

At 60 Hz: 587 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 720 m³/h

At 60 Hz: 745 m³/h

Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 114.4 W

At 60 Hz: 153.5 W

Rated current max.
At 50 Hz: 0.51 A

At 60 Hz: 0.68 A

Dimensions
Width: 323 mm

Height: 323 mm

Depth: 156 mm

Installation depth
136 mm
Mounting cut-out
Cut-out width: 292 mm

Cut-out height: 292 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 64 dB(A)

At 60 Hz: 66 dB(A)

Weight/pack
3.84 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997905
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 867/910 m³/h, 230 V, 1~, 50 Hz/60 Hz, WHD 323 x 323 x 156 mm, RAL 9005
Rittal SK 3244710
Rittal SK 3244710
Article number:
SK 3244.710
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, 1~ capacitor motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 700 m³/h

At 60 Hz: 770 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 867 m³/h

At 60 Hz: 910 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 537 m³/h

At 60 Hz: 587 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 720 m³/h

At 60 Hz: 745 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 120.7 W

At 60 Hz: 166.1 W

Rated current max.
At 50 Hz: 1.06 A

At 60 Hz: 1.47 A

Dimensions
Width: 323 mm

Height: 323 mm

Depth: 156 mm

Installation depth
136 mm
Mounting cut-out
Cut-out width: 292 mm

Cut-out height: 292 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 6 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 64 dB(A)

At 60 Hz: 66 dB(A)

Weight/pack
3.84 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997899
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 867/910 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 323 x 323 x 156 mm, RAL 7035
Rittal SK 3244718
Rittal SK 3244718
Article number:
SK 3244.718
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 9005
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, 1~ capacitor motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 700 m³/h

At 60 Hz: 770 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 867 m³/h

At 60 Hz: 910 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 537 m³/h

At 60 Hz: 587 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 720 m³/h

At 60 Hz: 745 m³/h

Rated operating voltage
115 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 120.7 W

At 60 Hz: 166.1 W

Rated current max.
At 50 Hz: 1.06 A

At 60 Hz: 1.47 A

Dimensions
Width: 323 mm

Height: 323 mm

Depth: 156 mm

Installation depth
136 mm
Mounting cut-out
Cut-out width: 292 mm

Cut-out height: 292 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature circuit-breaker/fuse: 6 A
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 64 dB(A)

At 60 Hz: 66 dB(A)

Weight/pack
3.84 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997882
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 867/910 m³/h, 115 V, 1~, 50 Hz/60 Hz, WHD 323 x 323 x 156 mm, RAL 9005
Rittal SK 3244740
Rittal SK 3244740
Article number:
SK 3244.740
Design
wall-mounted
Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
Benefits
Maximum air throughput via pleated filter included in the delivered state
Easy filter changes, thanks to a new opening mechanism on the louvred grille
Faster installation on the enclosure with optimised detent hooks
Diagonal fan technology achieves more even and constant ventilation of the enclosure, thanks to improved pressure stability
Tool-free assembly
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Diagonal, three-phase motor
Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 700 m³/h

At 60 Hz: 770 m³/h

Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 867 m³/h

At 60 Hz: 910 m³/h

Air throughput with matching outlet filter including chopped-fibre filter
At 50 Hz: 537 m³/h

At 60 Hz: 587 m³/h

Air throughput with matching outlet filter including pleated filter
At 50 Hz: 720 m³/h

At 60 Hz: 745 m³/h

Rated operating voltage
400 V, 3~, 50 Hz/60 Hz
460 V, 3~, 60 Hz
Power consumption Pel
At 50 Hz: 116.9 W

At 60 Hz: 165.6 W

Rated current max.
At 50 Hz: 0.22 A

At 60 Hz: 0.28 A

Dimensions
Width: 323 mm

Height: 323 mm

Depth: 156 mm

Installation depth
136 mm
Mounting cut-out
Cut-out width: 292 mm

Cut-out height: 292 mm

IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP55 with pleated filter and absorber mat
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3
Type 3R
Type 4
Type 4X with chopped-fibre filter/pleated filter and hose-proof hood
Note
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
Operating temperature range
-30 °C...55 °C
Storage temperature range
-30 °C...70 °C
Noise level
At 50 Hz: 64 dB(A)

At 60 Hz: 66 dB(A)

Weight/pack
3.64 kg
Packs of
1 pc(s).
Customs tariff number
84145915
EAN
4028177997875
ETIM 8
EC000320
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Blue e+ fan-and-filter unit, 867/910 m³/h, 400 V, 3~, 50 Hz/60 Hz, WHD 323 x 323 x 156 mm, RAL 7035

Get Blue e+ fan-and-filter unit Pricing

To receive Rittal Blue e+ fan-and-filter unit price, please send us a message >

Scroll to Top